Network-Enabled M Series Rack PDU User Manual
- 12 -
3. Ensure conductors are stripped adequately, exposing 15mm of copper.
4. Conductors shall be connected in-line with the terminal markings provided as
shown below (Line 1 = X; Line 2 = Y; Line 3 Z). Ensure screws are secure for
each conductor by applying a torque of 2.3 N-m (20 in-lb.).
5. Ensure conductors have enough slack (none should be under tension).
6. Feed grommet cap down cord and secure to input gland. Reference the table
below to ensure the grommet cap is torqued correctly.